Home > Temperature Transmitters > Temperature Transmitter
Parameters
(1) Temperature
Range (can be set through a dial switch): 0~+50 ℃/ -20~+80 ℃/ -40~+60 ℃/ customized
Accuracy: ± 0.3 ℃ (typical value)
Resolution: 0.1 ℃
Long term stability:<0.1 ℃/year
(2) Relative humidity
Range: 0-100% RH
Accuracy (including nonlinearity, hysteresis, and repeatability): ± 3% RH
Factory calibration uncertainty: ± 0.6% RH (0-40% RH)/± 1.0% RH (40-97% RH)
Response time (90%) Static air: 8s
Resolution: 0.1% RH
Long term stability: <0.5% RH/year
Work environment
Working environment temperature: -40~80 ℃
Working environment humidity: 0-99.9% non-condensing
Storage range: temperature: 0-60 ℃; Humidity: <90% RH
Working voltage: 12-36VDC
Power on time: 3s
Product power consumption: 15mA (typical)
Output signal: 0-5V; 0-10V; 4-20mA; RS485; Relay output